Opened 4 months ago

#663 new task

Let's get the space up to fire code

Reported by: m Owned by:
Priority: critical Milestone:
Component: Meatspace Keywords:
Cc:

Description

We had a fire marshall come in the other day and tell us everything we're doing wrong:

FIRE EXTINGUISHERS:
Fail
ITEM: *351 - Fire extinguishers must be inspected annually, then tagged and dated by a
1 / 3
person possessing a SFD certificate to perform such work.
CODE: SFD HAZ # - 351 - Fire extinguishers must be inspected annually, then tagged
and dated by a person possessing a SFD certificate to perform such work. (21 SFC
906.2, Admin Rule 9.01 and 2021 NFPA 10) Note: New fire extinguisher(s) are
considered good for one year from date of purchase. Proof of date of purchase is
required.
Fail
ITEM: *358 - Relocate fire extinguisher(s) so they are properly mounted with the top of
the extinguisher not more than 5 ft above the floor (up to 40 lbs) or not more than 2.5 ft
above the floor (over 40 lbs), and the bottom at least 4 inches above the floor.
CODE: SFD HAZ # - 358 - Relocate fire extinguisher(s) so they are properly mounted
with the top of the extinguisher not more than 5 feet above the floor (up to 40 lbs) or not
more than 3½ feet above the floor (over 40 lbs), and the bottom at least 4 inches above
the floor (21 SFC 906.9)
PLASTER/GYPSUM WALL REPAIRS/FINISH:
Fail
ITEM: *651 - Repair the damaged plaster or gypsum wallboard with a fire-resistive
material equivalent to the surrounding surfaces
REMARK:
Failing plaster below skylight.
CODE: SFD HAZ # - 651 - Repair the damaged plaster or gypsum wallboard with a fire-
resistive material equivalent to the surrounding surfaces. (21 SFC 704.1, 704.3)

Attachments (1)

Inspection SFD-2025-0018731.pdf (116.7 KB ) - added by m 4 months ago.

Download all attachments as: .zip

Change History (1)

Note: See TracTickets for help on using tickets.